GTH series thermal relay is used in the circuit of 50/60Hz, rated insulation voltage 660V,rated current 0.1-85A for protecting the phase break when the electric motor is overloaded. Therelay has different mechanism and temperature compensation. It can be plugged in CJX5 seriesAC contactor. The product conforms to IEC60947-4-1.
Motion Characteristic: Three-phase Balance Motion Tim
No |
Times of the setting current(A) |
Motion time |
Start conidition |
Ambient temperature |
||
1 |
1.05 |
>2h |
Cold state |
20±5oC |
||
2 |
1.2 |
<2h |
Heat state (Following the No.1 test) |
|||
3 |
1.5 |
<4min |
||||
4 |
7.2 |
10A |
2s< Tp ≤10s |
≤63A |
Cold state |
|
10 |
4s< Tp ≤10s |
>63A |
No |
Times the setting current(A) |
Motion time |
Start condition |
Ambient temperature |
|
Any two phases |
Another phase |
||||
1 |
1.0 |
0.9 |
>2h |
Cold state |
20±5oC |
2 |
1.15 |
0 |
<2h |
Heat state(Following the No.1 test) |
Phase-losing Motion Characteristic
Ratings |
Type |
GTH-22 |
GTH-40 |
GTH-85 |
||||||
Nominal current |
Ranges |
Ranges |
Ranges |
|||||||
Min. |
Mid. |
Max. |
Min. |
Mid. |
Max. |
Min. |
Mid. |
Max. |
||
Rated current(A) |
0.14 |
0.1 |
0.14 |
0.16 |
|
|
|
|
|
|
0.21 |
0.16 |
0.21 |
0.25 |
|||||||
0.33 |
0.25 |
0.33 |
0.4 |
|||||||
0.52 |
0.4 |
0.52 |
0.63 |
|||||||
0.82 |
0.63 |
0.82 |
1 |
|||||||
1.3 |
1 |
1.3 |
1.6 |
|||||||
2.1 |
1.6 |
2.1 |
2.5 |
|||||||
3.3 |
2.5 |
3.3 |
4 |
|||||||
5 |
4 |
5 |
6 |
4 |
5 |
6 |
||||
6.5 |
5 |
6.5 |
8 |
5 |
6.5 |
8 |
||||
7.5 |
6 |
7.5 |
9 |
6 |
7.5 |
9 |
||||
8.5 |
7 |
8.5 |
10 |
7 |
8.5 |
10 |
7 |
8.5 |
10 |
|
11 |
9 |
11 |
13 |
9 |
11 |
13 |
9 |
11 |
13 |
|
15 |
12 |
15 |
18 |
12 |
15 |
18 |
12 |
15 |
18 |
|
19 |
16 |
19 |
22 |
16 |
19 |
22 |
16 |
19 |
22 |
|
22 |
|
|
|
18 |
22 |
26 |
18 |
22 |
26 |
|
30 |
24 |
30 |
36 |
24 |
30 |
36 |
||||
34 |
28 |
34 |
40 |
28 |
34 |
40 |
||||
42 |
|
|
|
34 |
42 |
50 |
||||
55 |
45 |
55 |
65 |
|||||||
65 |
54 |
65 |
75 |
|||||||
74 |
63 |
74 |
85 |
|||||||
Element No. |
2 heaters |
Standard |
Standard |
Standard |
||||||
3 heaters |
Option |
Option |
Option |
|||||||
Aux. Contact |
|
1NO 1NC |
1NO 1NC |
1NO 1NC |
||||||
Reset type |
Auto/Manual |
Auto/ Manual |
Auto/Manual |
|||||||
Power consumption |
1.8VA/heater |
1.8VA/heater |
1.8VA/heater |
|||||||
Separate mounting unit |
AZ-22H |
AZ-40H |
AZ-85H |
|||||||
Other model |
|
GTH-22/3 |
GTH-40/3 |
GTH-85/3 |
||||||
|
GTH-22 |
GTH-40 |
GTH-85 |
|||||||
|
GTH-22/L |
GTH-40/L |
GTH-85/L |
|||||||
Applied contactors |
|
GMC-9,12,18,22 |
GMC-32,40 |
GMC-50,65,75,85 |
I have a client in Iran. He want US-52 and SS-22 speed controller in October. I sent a PI to him after sending price and freight charge, but i forgot to add freight...
This month our company launched a voucher, in order to appreciate the support from clients. When the client's goods value reached the setted amount, the voucher will...
Winston Wish You Marry Christmas!
Time in a hurry, in the beginning of the new year, we will be better customer service, quality is our culture, to give customers what they want. Winston returen work...